ENERZIP’s W Series uses Weichai gas engines. Our selection sheet lists 20 natural gas configurations from 16 to 1,400 kWe and five biogas configurations from 400 to 1,000 kWe, including 50 Hz and 60 Hz builds. ENERZIP manufactures and integrates the generator sets in China. ENERZIP AFRICA POWER SOLUTIONS handles regional sales, installation support, maintenance enquiries and spare parts from Zomba, Malawi.
W Series Natural Gas Generator Ratings

At 50 Hz, the W250N5 is rated at 200 kWe / 250 kVA, the W500N5 at 400 kWe / 500 kVA, and the W625N5 at 500 kWe / 625 kVA. The W1000N5 is rated at 800 kWe / 1,000 kVA. At a power factor of 0.8, 1,000 kWe corresponds to 1,250 kVA.
The selection sheet uses 400 V, three-phase, 0.8 power factor and a 40°C alternator reference temperature. Engine speed is 1,500 rpm at 50 Hz and 1,800 rpm at 60 Hz. The standby columns are estimates from ENERZIP’s selection sheet. The final datasheet states the approved rating. Dimensions are for preliminary layout and transport planning.
| Model | Continuous kWe | Continuous kVA | Standby est. kWe | Standby est. kVA | Weichai engine | STAMFORD 400 V | Frequency | Open L × W × H (mm) | Silent L × W × H (mm) / container |
|---|---|---|---|---|---|---|---|---|---|
| W20N5 | 16 | 20 | 16 | 20 | WP3ND20E300NG | PI 144D | 50 Hz | 1820 × 738 × 1084 | 2680 × 1100 × 1732 |
| W30N5 | 24 | 30 | 24 | 30 | WP3ND30E300NG | PI 144G | 50 Hz | 1820 × 738 × 1084 | 2680 × 1100 × 1732 |
| W60N5 | 50 | 62.5 | 55 | 68.75 | WP4D77E300NG | UCI 224F | 50 Hz | 1931 × 738 × 1086 | 2680 × 1100 × 1732 |
| W100N5 | 80 | 100 | 80 | 100 | WP6D132E300NG | UCI 274C | 50 Hz | 2532 × 950 × 1365 | 3970 × 1170 × 2222 |
| W150N5 | 120 | 150 | 128 | 160 | WP10D200E300NG | UCI 274F | 50 Hz | 2667 × 950 × 1322 | 3970 × 1170 × 2222 |
| W250N5 | 200 | 250 | 200 | 250 | WP13D317E300NG | UCDI 274K | 50 Hz | 3110 × 1134 × 1450 | 4215 × 1400 × 2250 |
| W500N5 | 400 | 500 | 400 | 500 | 6M33D450E310NG | HCI 544C | 50 Hz | 3600 × 1680 × 2117 | 4500 × 1900 × 2750 |
| W625N5 | 500 | 625 | 522 | 652.5 | 12M26D605E300NG | HCI 544F | 50 Hz | 3747 × 1486 × 1909 | 4615 × 1650 × 2530 |
| W1000N5 | 800 | 1,000 | 824 | 1,030 | 12M33D900E310NG | HCI 634J | 50 Hz | 5500 × 2000 × 2100 | ISO 20 ft container |
| W1375N5 | 1,100 | 1,375 | 1,120 | 1,400 | 16M33D1280NG10 | PI 734B | 50 Hz | 6090 × 2300 × 2900 | ISO 40 ft container |
| W1375N5 | 1,100 | 1,375 | 1,100 | 1,375 | 16M33D1150E500NG | PI 734B | 50 Hz | 6090 × 2300 × 2900 | ISO 40 ft container |
| W1750N5 | 1,400 | 1,750 | 1,508 | 1,885 | 12M55D1588A0NG | PI 734E | 50 Hz | 6090 × 2300 × 2900 | ISO 40 ft container |
| W60N6 | 50 | 62.5 | 50 | 62.5 | WP4D77E301NG | UCI 224D | 60 Hz | 1931 × 738 × 1086 | 2680 × 1100 × 1732 |
| W100N6 | 80 | 100 | 80 | 100 | WP6D132E301NG | UCI 224G | 60 Hz | 2532 × 950 × 1365 | 3970 × 1170 × 2222 |
| W181N6 | 145 | 181.25 | 159 | 198.75 | WP10D238E301NG | UCI 274G | 60 Hz | 2667 × 950 × 1322 | 3970 × 1170 × 2222 |
| W256N6 | 205 | 256.25 | 225 | 281.25 | WP13D317E301NG | UCDI 274J | 60 Hz | 3110 × 1134 × 1450 | 4215 × 1400 × 2250 |
| W500N6 | 400 | 500 | 400 | 500 | 6M33D480E311NG | HCI 444F | 60 Hz | 3600 × 1680 × 2117 | 4500 × 1900 × 2750 |
| W688N6 | 550 | 687.5 | 570 | 712.5 | 12M26D660E301NG | HCI 544F | 60 Hz | 3747 × 1486 × 1909 | 4615 × 1650 × 2530 |
| W1063N6 | 850 | 1,062.5 | 912 | 1,140 | 12M33D960E311NG | HCI 634J | 60 Hz | 5500 × 2000 × 2100 | ISO 20 ft container |
| W1375N6 | 1,100 | 1,375 | 1,100 | 1,375 | 16M33D1280NG11 | HCI 634K | 60 Hz | 6090 × 2300 × 2900 | ISO 40 ft container |
The two W1375N5 rows show the same 1,100 kWe / 1,375 kVA continuous rating. One uses the 16M33D1280NG10 and the other the 16M33D1150E500NG. Include the full engine model when requesting parts or a fuel-consumption curve.
W Series Biogas Generator Ratings

The 50 Hz biogas selection includes the 400 kWe W500G5B, 800 kWe W1000G5B and 1,000 kWe W1250G5B. The B suffix identifies biogas. The preceding 5 or 6 identifies 50 Hz or 60 Hz.
| Model | Continuous kWe | Continuous kVA | Standby est. kWe | Standby est. kVA | Weichai engine | STAMFORD 400 V | Frequency | Open L × W × H (mm) | Silent L × W × H (mm) / container |
|---|---|---|---|---|---|---|---|---|---|
| W500G5B | 400 | 500 | 400 | 500 | 6M33D450A0BG | HCI 544C | 50 Hz | 3600 × 1680 × 2117 | 4500 × 1900 × 2750 |
| W1000G5B | 800 | 1,000 | 824 | 1,030 | 12M33D880A0BG | HCI 634J | 50 Hz | 5500 × 2000 × 2100 | ISO 20 ft container |
| W1250G5B | 1,000 | 1,250 | 1,008 | 1,260 | 16M33D1150A0BG | PI 734A | 50 Hz | 6090 × 2300 × 2900 | ISO 40 ft container |
| W1063G6B | 850 | 1,062.5 | 912 | 1,140 | 12M33D960A1BG | HCI 634J | 60 Hz | 5500 × 2000 × 2100 | ISO 20 ft container |
| W1250G6B | 1,000 | 1,250 | 1,000 | 1,250 | 16M33D1150A0BG | HCI 634J | 60 Hz | 6090 × 2300 × 2900 | ISO 40 ft container |
The W1250G6B row follows the ENERZIP sheet and Weichai’s current table, which list 16M33D1150A0BG at 1,800 rpm. An earlier Weichai listing gives 16M33D1150A1BG for that speed. We confirm the engine suffix on the factory build sheet for a 60 Hz order.
Four ENERZIP 1 MW Gas Generator Sets Compared

These four ENERZIP configurations are specified at 1,000 kWe / 1,250 kVA and 50 Hz. The W1250N5 is ENERZIP’s published 6.3 kV natural gas project build. The W1375N5 above is a 400 V, 1,100 kWe build. The two configurations discussed here use the same 16M33D1280NG10 engine, with different alternators and electrical ratings.
| Fuel | ENERZIP model | Engine | Engine output at 1,500 rpm | Electrical output | Voltage and alternator |
|---|---|---|---|---|---|
| Natural gas | C1250G5N | Cummins K50N-G10 | 1,100 kWm | 1,000 kWe / 1,250 kVA | 400 V, STAMFORD PI 734A |
| Natural gas | W1250N5 | Weichai 16M33D1280NG10 | 1,280 kWm | 1,000 kWe / 1,250 kVA | 6.3 kV, ENGGA EG500-1000G/6300V |
| Biogas | C1250G5B | Cummins K50N-G10B | 1,100 kWm | 1,000 kWe / 1,250 kVA | 400 V, STAMFORD PI 734A |
| Biogas | W1250G5B | Weichai 16M33D1150A0BG | 1,150 kWm | 1,000 kWe / 1,250 kVA | 400 V, STAMFORD PI 734A |
Chongqing Cummins lists the K50N-G10 and K50N-G10B at 1,100 kWm continuous at 1,500 rpm, with a recommended generator output of 1,000 kWe for each. The K50N brochure shows separate jacket-water and aftercooler circuits. The ENERZIP C Series selection sheet also lists a K50N-G10H option for the C1250G5N.
Weichai lists the 16M33 gas platform as a 52.3 L, four-stroke V16 with a 150 mm bore and 185 mm stroke, four valves per cylinder, turbocharging and water-to-air charge cooling. Its product page lists electronic engine control, misfire monitoring and knock protection. The 16M33D1150A0BG is the biogas variant rated at 1,150 kWm at 1,500 rpm, paired with a recommended 1,000 kWe generator output.
Published Fuel Data for the 1 MW W1250N5
The published ENERZIP specification for the W1250N5 6.3 kV set gives a full-load fuel consumption reference of approximately 245–260 Nm³/h at 1,000 kWe, using natural gas with a lower heating value of 34.3 MJ/Nm³. The 16M33D1280NG10 engine datasheet gives the following fuel energy inputs and mechanical efficiencies at three load points, based on the engine’s 1,280 kWm continuous rating.
| Engine load | Fuel energy input, LHV basis | Engine mechanical efficiency |
|---|---|---|
| 100% | 3,056 kW | 41.8% |
| 75% | 2,387 kW | 40.2% |
| 50% | 1,675 kW | 38.2% |
For the C1250G5N, C1250G5B and W1250G5B, request a fuel-consumption curve for the exact engine and project fuel. A biogas enquiry should include measured methane and CO₂ content, available gas flow, H₂S, moisture and gas pressure after treatment. For natural gas, include the supplier’s gas analysis or heating value and the inlet pressure available under load.
Two ENERZIP Biogas CHP Packages
Hot-Water Recovery
A stainless-steel plate heat exchanger transfers jacket-water heat into the site water circuit. An exhaust heat exchanger can supply additional hot-water duty. On a farm, the water can serve digester heating or process wash water. Specify the supply temperature, return temperature and water flow so the heat exchanger can be sized for the actual circuit.
Steam Recovery
The steam package uses a waste-heat steam generator on the engine exhaust. Jacket-water heat can serve a separate hot-water circuit or preheat boiler feedwater if the arrangement calls for it. For a steam quote, give the required steam flow in kg/h, working pressure and feedwater temperature. Steam output is calculated from the engine exhaust data and boiler conditions for the quoted project.
Main CHP Equipment
| No. | Component | Function |
|---|---|---|
| 1 | Exhaust heat recovery unit | Transfers engine exhaust heat to the hot-water or steam recovery package. |
| 2 | Stainless-steel plate heat exchanger | Transfers jacket-water heat to a separate site water circuit. |
| 3 | Automatic jacket-water temperature control valve | Modulates flow through the jacket-water circuit. |
| 4 | High-temperature circulation pump | Circulates water through the heat recovery loop. |
| 5 | CHP control system | Provides automatic and manual settings, operating data and alarms through the touchscreen. |
CHP Touchscreen Settings
This table transcribes the values displayed on the ENERZIP CHP touchscreen in the project photo. The settings for an ordered package are established during commissioning.
| HMI section | Function | Displayed setting or page |
|---|---|---|
| Automatic | Jacket-water proportional valve temperature settings | 95°C at 100%. 75°C at 0%. |
| Automatic | Exhaust three-way valve temperature settings | 45°C at 0%. 23°C at 100%. |
| Automatic | Circulation pump frequency settings | 45 Hz and 5 Hz |
| Manual | Boiler water level setting | 25 cm |
| Manual | Variable-frequency drive setting | 20 Hz |
| Manual | Jacket-water proportional valve position | 50% |
| Manual | Exhaust three-way valve position | 65% |
| Alarm protection | Steam pressure alarm | 0.2 MPa |
| Alarm protection | Steam temperature alarm | 95.0°C |
| Alarm protection | Circulating water pressure alarm | 0.2 MPa |
| Alarm protection | Engine outlet water temperature alarm | 88.0°C |
| Navigation | Operator pages | Main screen, data calibration, operating data and alarm collection |
The steam pressure and temperature entries are separate alarm fields as displayed on the touchscreen. The steam delivery specification is stated on the approved boiler datasheet.
Exhaust Aftertreatment for European Projects
ENERZIP can include exhaust aftertreatment in the project quotation. An oxidation catalyst can be specified for CO and, with a suitable catalyst, formaldehyde control. Selective catalytic reduction (SCR) is an option for NOₓ control on a lean-burn engine. The catalyst, silencer, boiler and pipework all contribute to exhaust backpressure. The package design checks the combined pressure drop against the engine limit and the catalyst temperature at the expected loads.
The EU Medium Combustion Plant Directive uses rated thermal input for its 1–50 MWth scope. The applicable emissions conditions depend on the installation country, fuel and permit. In Germany, Section 16 of the 44th BImSchV includes formaldehyde provisions for combustion engines. For a steam package supplied to the EU, check the applicability of the Pressure Equipment Directive to the equipment and assembly.
ENERZIP Africa Sales and Service
Our Zomba team serves Malawi, Mozambique, Tanzania, Zambia and Zimbabwe. For a quotation, send the project location, required electrical output, voltage, frequency, operating hours and gas analysis. For CHP, include the hot-water or steam conditions. The quotation records the agreed scope for commissioning support, maintenance and parts.