ENERZIP manufactures and integrates gas generator sets in China. ENERZIP AFRICA POWER SOLUTIONS supports customers from Zomba, Malawi, serving Malawi, Mozambique, Tanzania, Zambia and Zimbabwe. Our Cummins-powered C Series includes configurations for natural gas, liquefied petroleum gas (LPG), associated petroleum gas (APG) and treated biogas. The three selection tables below cover 60 configurations at 50 Hz and 60 Hz, with recommended continuous outputs from 250 to 1,200 kWe across the range.
A gas generator quotation starts with the fuel available at the site and the electrical load the generator must carry. A factory taking pipeline gas, an oilfield using associated gas and a farm running on digester gas can all ask for a 500 kW generator. Each project needs its own fuel specification, engine calibration and gas train. The site’s operating hours, largest motor loads and maintenance arrangements also affect which configuration makes sense.
How to Read an ENERZIP Cummins Gas Generator Model Number
In C625G5N, C identifies the Cummins engine series, 625 is the nominal 625 kVA prime-power capacity class, G identifies the gas generator series, 5 means 50 Hz, and N means natural gas. At a power factor of 0.8, 625 kVA corresponds to 500 kWe.
| ENERZIP model | Frequency | Fuel | Cummins engine | Listed continuous output |
|---|---|---|---|---|
| C625G5N | 50 Hz | Natural gas | K38N-G5 | 500 kWe / 625 kVA |
| C625G6N | 60 Hz | Natural gas | K38N-G5S | 500 kWe / 625 kVA |
| C625G5P | 50 Hz | LPG or APG | K38N-G5P | 500 kWe / 625 kVA |
| C625G5B | 50 Hz | Biogas | K38N-G5B | 500 kWe / 625 kVA |
ENERZIP uses the prime-power capacity class in the model name so buyers have a starting point for sizing a set for normal operation. A model named around its emergency standby figure could lead a buyer to use that figure when sizing a daily operating load. Use the code to find the capacity class, then verify the operating duty and output against the quoted technical datasheet.
Some established codes use a nominal size. The C300G5P, for example, is listed at 250 kWe / 312.5 kVA continuous, and the C400G5B is listed at 300 kWe / 375 kVA continuous. Where a code covers two engine configurations, include the exact engine in your enquiry. The C1250G5N appears with both the K50N-G10 and K50N-G10H.
Continuous Output, Prime Power and Emergency Standby Power
kWe is the active electrical power supplied to the load. kVA is apparent power and is used to size the alternator, breakers, cables and switchgear. The conversion in the tables is kWe = kVA × 0.8. A 500 kWe load at 0.8 power factor corresponds to 625 kVA. A lower power factor increases the kVA required for the same kWe.
Prime Rated Power (PRP) applies to variable-load operation under the manufacturer’s rating conditions. Continuous Operating Power (COP) applies to continuous operation at the specified load and conditions. Emergency Standby Power (ESP) applies to emergency duty and has its own operating and load limits. The model name gives the nominal prime-power class, and the tables give the workbook’s recommended continuous electrical output. The quotation for the ordered set should identify the applicable duty and rating.
The standby columns are engineering estimates. The calculation uses the lowest of 110% of the listed continuous kWe, the selected alternator’s continuous kW rating, and 95% of the engine’s continuous shaft power. The 95% factor is a planning assumption for the conversion from shaft power to electrical output. The result is rounded down to a whole kWe, then divided by 0.8 to obtain estimated kVA. On some rows, the standby estimate equals the continuous rating. The confirmed ESP rating, where specified, is recorded in the final project datasheet.
The STAMFORD matches shown are for 400 V, three-phase, 0.8 power factor and a 40°C alternator reference condition. The 50 Hz sets run at 1,500 rpm, and the 60 Hz sets run at 1,800 rpm. Give us the actual site voltage when requesting a quote. The winding, engine rating and alternator capacity must be checked against the specified voltage, frequency, altitude and cooling air temperature.
Cummins Natural Gas Generator Sets — 24 Configurations

The natural gas group covers 300 to 1,200 kWe continuous. For a factory planning to run a 500 kWe load on pipeline gas at 50 Hz, the C625G5N is a starting point. If the plant can draw sustained loads above 500 kWe, or a compressor bank starts while other equipment is running, use the full load profile to check the next size and the largest load step.
For pipeline natural gas, provide the gas composition or the supplier’s specification, the maximum flow the line can deliver, and the minimum pressure at the generator inlet while other site consumers are running. A pressure reading taken with all equipment stopped gives only part of the picture. For regasified LNG, confirm who is supplying the vaporization and pressure regulation equipment and where the connection to the generator package will be made.
| Model | Frequency | Continuous kWe | Continuous kVA | Standby est. kWe | Standby est. kVA | Cummins engine | STAMFORD 400 V | Open L × W × H (mm) | Silent L × W × H (mm) / Container |
|---|---|---|---|---|---|---|---|---|---|
| C375G5N | 50 Hz | 300 | 375 | 320 | 400 | K19N-G1 | HCI 444F | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C438G5N | 50 Hz | 350 | 437.5 | 373 | 466.25 | K19N-G3 | HCI 544C | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C500G5N | 50 Hz | 400 | 500 | 400 | 500 | K19N-G4 | HCI 544C | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C625G5N | 50 Hz | 500 | 625 | 536 | 670 | K38N-G5 | HCI 544F | 4200 × 2300 × 2100 | 4300 × 2400 × 2300 |
| C750G5N | 50 Hz | 600 | 750 | 646 | 807.5 | K38N-G6 | HCI 634G | 4315 × 2020 × 2235 | 4515 × 2420 × 2435 |
| C875G5N | 50 Hz | 700 | 875 | 745 | 931.25 | K38N-G7 | HCI 634H | 4315 × 2020 × 2235 | 4515 × 2020 × 2535 |
| C1000G5N | 50 Hz | 800 | 1,000 | 824 | 1,030 | K38N-G8 | HCI 634J | 4280 × 1960 × 2310 | 4580 × 1960 × 2510 |
| C1125G5N | 50 Hz | 900 | 1,125 | 908 | 1,135 | K50N-G9 | HCI 634K | 4200 × 2060 × 2165 | ISO 20 ft Container |
| C1250G5N | 50 Hz | 1,000 | 1,250 | 1,008 | 1,260 | K50N-G10 | PI 734A | 4200 × 2060 × 2165 | ISO 40 ft Container |
| C1250G5N | 50 Hz | 1,000 | 1,250 | 1,008 | 1,260 | K50N-G10H | PI 734A | 4200 × 2060 × 2165 | ISO 40 ft Container |
| C1375G5N | 50 Hz | 1,100 | 1,375 | 1,120 | 1,400 | K50N-G11H | PI 734B | 4950 × 2000 × 2580 | ISO 40 ft Container |
| C1500G5N | 50 Hz | 1,200 | 1,500 | 1,235 | 1,543.75 | K50N-G12H | PI 734C | 5420 × 2140 × 2500 | ISO 40 ft Container |
| C375G6N | 60 Hz | 300 | 375 | 325 | 406.25 | K19N-G2 | HCI 444F | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C438g6N | 60 Hz | 350 | 437.5 | 373 | 466.25 | K19N-G3S | HCI 444F | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C500G6N | 60 Hz | 400 | 500 | 400 | 500 | K19N-G4S | HCI 444F | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C625G6N | 60 Hz | 500 | 625 | 500 | 625 | K38N-G5S | HCI 544D | 4200 × 2300 × 2100 | 4300 × 2400 × 2300 |
| C750G6N | 60 Hz | 600 | 750 | 646 | 807.5 | K38N-G6S | HCI 544F | 4315 × 2020 × 2235 | 4515 × 2420 × 2435 |
| C875G6N | 60 Hz | 700 | 875 | 700 | 875 | K38N-G7S | HCI 634G | 4315 × 2020 × 2235 | 4515 × 2020 × 2535 |
| C1000G6N | 60 Hz | 800 | 1,000 | 800 | 1,000 | K38N-G8S | HCI 634H | 4280 × 1960 × 2310 | 4580 × 1960 × 2510 |
| C1125G6N | 60 Hz | 900 | 1,125 | 940 | 1,175 | K50N-G9S | HCI 634J | 4200 × 2060 × 2165 | ISO 20 ft Container |
| C1250G6N | 60 Hz | 1,000 | 1,250 | 1,000 | 1,250 | K50N-G10S | HCI 634J | 4200 × 2060 × 2165 | ISO 40 ft Container |
| C1250G6N | 60 Hz | 1,000 | 1,250 | 1,000 | 1,250 | K50N-G10SH | HCI 634J | 4200 × 2060 × 2165 | ISO 40 ft Container |
| C1375G6N | 60 Hz | 1,100 | 1,375 | 1,100 | 1,375 | K50N-G11SH | HCI 634K | 4950 × 2000 × 2580 | ISO 40 ft Container |
| C1500G6N | 60 Hz | 1,200 | 1,500 | 1,235 | 1,543.75 | K50N-G12SH | PI 734B | 5420 × 2140 × 2500 | ISO 40 ft Container |
Cummins LPG and Associated Petroleum Gas Generator Sets — 20 Configurations
The P group lists configurations from 250 to 1,000 kWe continuous for LPG or APG projects. LPG consists mainly of propane and butanes. Associated petroleum gas is produced alongside crude oil, and its composition can vary by source. The P suffix identifies the product group. When requesting a quotation, specify the fuel the machine will run on so the engine calibration and gas system can be selected for that supply.
For an LPG installation, send the propane-to-butane blend, delivery arrangement and available vapor supply under the expected operating conditions. For an APG project, send a recent gas analysis and describe any known changes in composition, pressure or available flow. Include available information on heavier hydrocarbons, hydrogen sulfide and liquid carryover. These details help define the gas conditioning and gas train and establish the output that can be quoted for the site fuel.
The engine choice can also change the layout. At 50 Hz, the C875G5P is listed with either a K38N-G7P or a K50N-G7P. Both rows show 700 kWe / 875 kVA continuous. The K38 row shows a silent canopy with reference dimensions, and the K50 row shows a reference 20 ft container. Include the engine code in a tender or request both options if either layout can fit.
| Model | Frequency | Continuous kWe | Continuous kVA | Standby est. kWe | Standby est. kVA | Cummins engine | STAMFORD 400 V | Open L × W × H (mm) | Silent L × W × H (mm) / Container |
|---|---|---|---|---|---|---|---|---|---|
| C300G5P | 50 Hz | 250 | 312.5 | 273 | 341.25 | K19N-G1P | HCI 444E | 3900 × 1700 × 1850 | 4300 × 2100 × 2300 |
| C375G5P | 50 Hz | 300 | 375 | 320 | 400 | K19N-G2P | HCI 444F | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C625G5P | 50 Hz | 500 | 625 | 536 | 670 | K38N-G5P | HCI 544F | 4200 × 2300 × 2100 | 4300 × 2400 × 2300 |
| C750G5P | 50 Hz | 600 | 750 | 646 | 807.5 | K38N-G6P | HCI 634G | 4315 × 2020 × 2235 | 4515 × 2420 × 2435 |
| C875G5P | 50 Hz | 700 | 875 | 745 | 931.25 | K38N-G7P | HCI 634H | 4315 × 2020 × 2235 | 4515 × 2020 × 2535 |
| C1000G5P | 50 Hz | 800 | 1,000 | 824 | 1,030 | K38N-G8P | HCI 634J | 4280 × 1960 × 2310 | 4580 × 1960 × 2510 |
| C875G5P | 50 Hz | 700 | 875 | 745 | 931.25 | K50N-G7P | HCI 634H | 4200 × 2060 × 2165 | ISO 20 ft Container |
| C1000G5P | 50 Hz | 800 | 1,000 | 824 | 1,030 | K50N-G8P | HCI 634J | 4200 × 2060 × 2165 | ISO 20 ft Container |
| C1125G5P | 50 Hz | 900 | 1,125 | 908 | 1,135 | K50N-G9P | HCI 634K | 4200 × 2060 × 2165 | ISO 20 ft Container |
| C1250G5P | 50 Hz | 1,000 | 1,250 | 1,008 | 1,260 | K50N-G10P | PI 734A | 4200 × 2060 × 2165 | ISO 40 ft Container |
| C300G6P | 60 Hz | 250 | 312.5 | 273 | 341.25 | K19N-G1PS | HCI 444D | 3900 × 1700 × 1850 | 4300 × 2100 × 2300 |
| C375G6P | 60 Hz | 300 | 375 | 325 | 406.25 | K19N-G2PS | HCI 444F | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C625G6P | 60 Hz | 500 | 625 | 500 | 625 | K38N-G5PS | HCI 544D | 4200 × 2300 × 2100 | 4300 × 2400 × 2300 |
| C750G6P | 60 Hz | 600 | 750 | 646 | 807.5 | K38N-G6PS | HCI 544F | 4315 × 2020 × 2235 | 4515 × 2420 × 2435 |
| C875G6P | 60 Hz | 700 | 875 | 700 | 875 | K38N-G7PS | HCI 634G | 4315 × 2020 × 2235 | 4515 × 2020 × 2535 |
| C1000G6P | 60 Hz | 800 | 1,000 | 800 | 1,000 | K38N-G8PS | HCI 634H | 4280 × 1960 × 2310 | 4580 × 1960 × 2510 |
| C875G6P | 60 Hz | 700 | 875 | 700 | 875 | K50N-G7PS | HCI 634G | 4200 × 2060 × 2165 | ISO 20 ft Container |
| C1000G6P | 60 Hz | 800 | 1,000 | 800 | 1,000 | K50N-G8PS | HCI 634H | 4200 × 2060 × 2165 | ISO 20 ft Container |
| C1125G6P | 60 Hz | 900 | 1,125 | 940 | 1,175 | K50N-G9PS | HCI 634J | 4200 × 2060 × 2165 | ISO 20 ft Container |
| C1250G6P | 60 Hz | 1,000 | 1,250 | 1,000 | 1,250 | K50N-G10PS | HCI 634J | 4200 × 2060 × 2165 | ISO 40 ft Container |
Cummins Biogas Generator Sets — 16 Configurations

The biogas configurations in this table cover 300 to 1,000 kWe continuous. The B suffix identifies biogas builds, including models on the K19N, K38N and K50N engine platforms. These configurations can be considered for livestock digesters and wastewater treatment plants where the available treated gas meets the selected engine’s specification.
For a biogas quote, send measured gas flow, methane and CO₂ content, hydrogen sulfide, moisture or dew point, and the pressure available after treatment. If possible, include readings from both normal and low-production periods. Check for siloxanes where the feedstock or wastewater gas may contain them. Plan condensate removal and gas treatment around the limits specified at the generator inlet.
If the project requires combined heat and power (CHP), specify where the recovered heat will go. A digester heating loop or process hot-water circuit has its own supply and return temperatures, flow and operating schedule. ENERZIP can specify exhaust and jacket-water heat recovery around that demand, with the thermal duty and equipment scope stated separately from the electrical output.
| Model | Frequency | Continuous kWe | Continuous kVA | Standby est. kWe | Standby est. kVA | Cummins engine | STAMFORD 400 V | Open L × W × H (mm) | Silent L × W × H (mm) / Container |
|---|---|---|---|---|---|---|---|---|---|
| C400G5B | 50 Hz | 300 | 375 | 320 | 400 | K19N-G1B | HCI 444F | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C438G5B | 50 Hz | 350 | 437.5 | 373 | 466.25 | K19N-G3B | HCI 544C | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C625G5B | 50 Hz | 500 | 625 | 536 | 670 | K38N-G5B | HCI 544F | 4200 × 2300 × 2100 | 4300 × 2400 × 2300 |
| C750G5B | 50 Hz | 600 | 750 | 646 | 807.5 | K38N-G6B | HCI 634G | 4315 × 2020 × 2235 | 4515 × 2420 × 2435 |
| C875G5B | 50 Hz | 700 | 875 | 745 | 931.25 | K38N-G7B | HCI 634H | 4315 × 2020 × 2235 | 4515 × 2020 × 2535 |
| C1000G5B | 50 Hz | 800 | 1,000 | 824 | 1,030 | K38N-G8B | HCI 634J | 4280 × 1960 × 2310 | 4580 × 1960 × 2510 |
| C1125G5B | 50 Hz | 900 | 1,125 | 908 | 1,135 | K50N-G9B | HCI 634K | 4200 × 2060 × 2165 | ISO 20 ft Container |
| C1250G5B | 50 Hz | 1,000 | 1,250 | 1,008 | 1,260 | K50N-G10B | PI 734A | 4200 × 2060 × 2165 | ISO 40 ft Container |
| C400G6B | 60 Hz | 300 | 375 | 325 | 406.25 | K19N-G2B | HCI 444F | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C438G6B | 60 Hz | 350 | 437.5 | 373 | 466.25 | K19N-G3BS | HCI 444F | 3900 × 1700 × 1850 | 4400 × 2100 × 2450 |
| C625G6B | 60 Hz | 500 | 625 | 500 | 625 | K38N-G5BS | HCI 544D | 4200 × 2300 × 2100 | 4300 × 2400 × 2300 |
| C750G6B | 60 Hz | 600 | 750 | 646 | 807.5 | K38N-G6BS | HCI 544F | 4315 × 2020 × 2235 | 4515 × 2420 × 2435 |
| C875G6B | 60 Hz | 700 | 875 | 700 | 875 | K38N-G7BS | HCI 634G | 4315 × 2020 × 2235 | 4515 × 2020 × 2535 |
| C1000G6B | 60 Hz | 800 | 1,000 | 800 | 1,000 | K38N-G8BS | HCI 634H | 4280 × 1960 × 2310 | 4580 × 1960 × 2510 |
| C1125G6B | 60 Hz | 900 | 1,125 | 940 | 1,175 | K50N-G9BS | HCI 634J | 4200 × 2060 × 2165 | ISO 20 ft Container |
| C1250G6B | 60 Hz | 1,000 | 1,250 | 1,000 | 1,250 | K50N-G10BS | HCI 634J | 4200 × 2060 × 2165 | ISO 40 ft Container |
How to Select the Right Gas Generator for Your Site
- Identify the fuel and the available supply. Send the gas analysis, flow, inlet pressure range and details of any drying, filtration or desulfurization equipment. If you report gas flow in Nm³/h, include the reference conditions used. When comparing gas availability with expected consumption, use the same reference conditions and heating-value basis.
- Build an electrical load list. Include normal operating kW, maximum simultaneous demand, power factor and the largest loads that start together. For pumps, refrigeration compressors and large fans, include the starting method and the starting current or kVA if available. On an islanded generator, the alternator must handle the starting current and the engine must respond to the load step.
- Specify the operating duty and site conditions. Provide the expected annual operating hours, typical loading pattern, altitude and maximum cooling air inlet temperature. Confirm whether the set will operate independently, in parallel with other generators or in parallel with the utility.
- Check the equipment layout. Use the open skid, silent canopy and container dimensions as reference sizes for preliminary planning. Some entries use the dimensions of a comparable engine platform and output class. Request the general arrangement drawing for the exact configuration before finalizing transport or construction. Check service door clearance, lifting points, ventilation, exhaust routing and the positions of gas and cable connections.
- Compare quotations on the same scope. Check the engine and alternator codes, operating duty, enclosure, controls, gas train, testing, delivery and installation responsibilities. Request gas consumption at full load and at the plant’s normal running load using the same fuel and measurement basis across quotations.
SmartGen, Deep Sea, DEIF and ComAp Controller Options
ENERZIP offers SmartGen, Deep Sea Electronics (DSE), DEIF and ComAp controller options. A stand-alone standby installation may need automatic mains failure detection and an interface to an automatic transfer switch. A parallel installation requires synchronization, breaker control, protection, and active and reactive load sharing. The controller also needs to support the engine ECU and the signals required by the site.
When a new generator will share load with existing equipment, send the site single-line diagram and the models of the controllers and breakers already installed. We can then check how the governor, voltage regulator and control interfaces will work together and quote the panel and commissioning scope with the generating set.
STAMFORD, ENERZIP, Leroy-Somer, Marathon and Engga Alternator Options
The tables show STAMFORD reference alternator matches. ENERZIP can also quote ENERZIP-series, Leroy-Somer, Marathon and Engga alternators where the required rating and build are available.
When changing the alternator, check the exact winding, rated voltage and frequency, operating duty and motor-starting requirement. An alternator change can also affect the coupling, skid and canopy dimensions. The final alternator model and general arrangement drawing identify what will be built.
When Two 200 kW Generators Make Sense Compared with One 400 kW Set
If a plant normally runs at or below 200 kW and only draws close to 400 kW during busy periods, compare two 200 kW gas generators in parallel with a single 400 kW set. Two standard machines can be less expensive in some quotations. The result depends on the engine options, canopy or container, freight and synchronizing switchgear. Compare the complete installed cost, including both sets, the panel, installation, testing and maintenance parts.
With a suitable controller and load profile, one generator can carry the lighter load and the second can start when demand increases. During maintenance, the remaining generator can supply priority loads within its site rating. A full 400 kW demand requires both 200 kW sets to be available. If the plant must retain 400 kW with one set out of service, size the installed capacity for that requirement. Also check how the system will respond if a unit trips while both generators are loaded or if a large motor must start before the second unit is online.
Sales, Commissioning and After-Sales Support from Malawi
ENERZIP AFRICA POWER SOLUTIONS supports projects in Malawi, Mozambique, Tanzania, Zambia and Zimbabwe from Zomba. Our regional team reviews the electrical load and fuel data with the factory, confirms the requested build and coordinates installation and commissioning within the agreed project scope. Where the project requires factory acceptance testing, on-site commissioning, operator training or an initial spare-parts package, we list those items in the quotation so the buyer can see who is responsible for each step.
For maintenance planning, request the service schedule and consumables list for the exact engine supplied. Compare oil, filters, spark plugs and service labor over the same number of operating hours when reviewing different configurations. Agree on the parts package, expected delivery and site service arrangements before the first scheduled outage.
Request a gas generator quotation. Send your project location, fuel type, gas analysis and available flow, required continuous kW, voltage, frequency, largest motor load and expected operating hours. If you have selected a row from the tables, include both the ENERZIP generator model and the Cummins engine model in your enquiry.